4.3 Combustion OUTPUT FORM
Outputs
CO
2
(Carbon Dioxide) e %CO
2
in the combustion products.
Excess O
2
(Excess Air) e amount of O
2
above the minimum theoreti-
cal amount needed for complete combustion. For complete and ecient
combustion, Excess O
2
must be adjusted to manufacturers specica-
tions.
COAF (Carbon Monoxide Air Free) e amount of CO in the combustion
products taking into account the dilution eect of excess O
2
.
Net Temp (Net Temperature) e stack (vent) temperature minus the pri-
mary air temperature.
Standard E (Eciency) e actual eciency of the combustion equip-
ment calculated by analyzing the losses up the exhaust.
Siegert E (Eciency) e European standard for combustion eciency.
See Sec (See Section) e section numbers on the OUTPUT FORM refer to
the sections in this manual with more detailed information about each
test.
Atmospheric Fan Assisted Natural Gas or LPG
Oxygen (O
2
) 6-9%
Stack Temperature 325-500°F
Condensing Natural Gas or LG
Oxygen (O
2
) 6-9%
Stack Temperature 90-140°F
Natural Gas/LPG Power Burners
Oxygen (O
2
) 3-6%
Stack Temperature 275-500°F
Fuel oil Flame Retention Power Burners
Oxygen (O
2
) 3-7%
Stack Temperature 325-500°F
Fuel Oil Non-Flame Retention Power Burners
Oxygen (O
2
) 6-9%
Stack Temperature 400-600°F
Condensing Oil
Oxygen (O
2
) 3-7%
Stack Temperature 90-140°F
Combustion OUTPUT FORM.
Appropriate levels for combustion equipment chart.
Manufacturer's specifications should always be
determined before adjusting the system.
The OUTPUT FORM displays the
results of the test. Standard
Efficiency should be close to
manufacturer's specifications.