SPECIFICATIONS
Display: 3¾ digit liquid crystal display (LCD) with a maxi-
mum reading of 3999.
Overrange: "OL" or “-OL” mark indication.
Auto power off: 10 minutes.
Operating environment: 32 to 122°F (0 to 50°C), at <70%
R.H.
Storage temperature: -4 to 140°F (-20 to 60°C), @ <80%
R.H. with batteries removed.
Accuracy: Specifications good in ambient conditions of
74°F ±8°F (23°C ±4°C), <75% relative humidity.
Temperature coefficient:0.1×(specified accuracy) per
°F/°C; 32 to 66°F (0 to 19°C); 82 to 122°F(28 to 50°C).
Altitude: 6561.7 feet (2000m).
Jaw opening capability: 30mm (diameter) conductor
Power: Three lithium-ion CR2032 3V batteries.
Battery life: 100 hours typical for lithium-ion on AAC (top
display), 75 hours typical for lithium-ion on dial functions
(bottom display).
Accessories: One pair vinyl test leads, ATB1 k-type ther-
mocouple (SC53), (3) 3V CR2032 batteries (installed),
ANC4 carrying case, and operating instructions.
Safety: IEC/EN 61010-1 (UL61010-1) CATIII
600V and IEC/EN 61010-2-032 (UL61010-2-032)
CATIII 300V, class II and pollution degree 2
indoor use comply with CE, C-tick certified.
DC Volts
Ranges: 4V, 40V, 400V, 600V
Resolution: 1mV
Accuracy: ±(0.5% rdg + 2 dgts)
Input impedance: 4V: 10MΩ
40V~600V: 9.1MΩ
AC Volts (50Hz - 500Hz)
Ranges: 4V, 40V, 400V, 600V
Resolution: 1mV
Accuracy: ±(1.2% rdg + 5 dgts),
±(1.5% rdg + 5 dgts) on 600V range
Input impedance:
4V: 10MΩ
40V~600V: 9.1MΩ
Minimum test time for stable reading: 2 seconds
Resistance
Ranges: 400Ω, 4kΩ, 40kΩ, 400kΩ, 4MΩ, 40MΩ
Resolution: 0.1Ω
Accuracy:
±(1.0% rdg + 4 dgts) on 400Ω to 400kΩ ranges
±(1.5% rdg + 4 dgts) on 4MΩ range
±(3.0% rdg + 5 dgts) on 40MΩ range
Open circuit volts: -0.45VDC typical, (-1.2VDC on
400Ω range)
Minimum test time for stable reading: 2 seconds
AC Current (50Hz - 60Hz)
Ranges: 40A, 400A
Resolution: 0.01A
Accuracy: ±(2.0% rdg + 6 dgts)
DC Current (SC52)
Ranges: 400μA, 4000μA
Resolution: 0.1μA
Accuracy: ±(1.0% rdg + 2 dgts)
Voltage burden: 1V (8V on 4000μA range)
Capacitance (SC53)
Range: 4μF, 4 0μF, 400μF, 4mF
4.000mF = 4000μF
Resolution: 1.0nF
Accuracy: ±(3% rdg + 10 dgts) on 4μF
±(3% rdg + 5 dgts) on 40μF to 400μF
±(5% rdg + 20 dgts) on 4mF (4000μF)
Minimum input range: >100nF
Safety: “dsc” symbol on LCD indicates that the
capacitor must be discharged before testing.
Continuity
Range: 400Ω
Resolution: 1Ω
Audible indication: Less than 25Ω
Response time: 500ms
Diode Test (SC52)
Test current: 1.2mA (approximate)
Accuracy: ±(3.0% rdg + 3 dgts)
Resolution: 10mV
Audible indication: Less than 0.25V
Open circuit volts: 3.0VDC typical
Temperature (SC53)
Range: -30 to 400°F (-34 to 204°C)
Resolution: 0.1°
Accuracy: ±1°F (32 to 120°F); ±0.5°C (0 to 49°C),
±1% + 1.5°F (-4 to 400°F);
±1% + 1°C (-20 to 204°C),
±2% + 4°F (-30 to -4°F);
±2% + 2°C (-34 to -20°C).
Sensor type: K-type thermocouple
Voltage
Amps AC Through Clamp
Resistance
Capacitance
Microamps (for flame diode)